A flexible duct smoke detector that can fit square or rectangular configurations.
Description:
The InnovairFlex D4120 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance.
Product Features:
- 4-Wire Photoelectric, integrated low-flow technology
- Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/sec)
- Versatile mounting options: square or rectangular configuration
- Plug-in sensor offers superb false alarm immunity and the latest sensor technology
- Broad ranges for operating temperature (–4°F to 158°F) and humidity (0% to 95% non-condensing)
- Patented sampling tube installs from front or back of the detector with no tools required
- Increased wiring space with a newly added 3⁄4-inch conduit knockout
- One easy-access Test/Reset button and improved LED status
- Patented interconnect feature for multi-fan shutdown
- New high contrast terminal designations
- Built-in short circuit protection from operator wiring errors
- Field selectable settings for configuring the detector
- Two DPDT Form-C relay contacts
- 24 VAC/DC or 120 VAC
- Backward compatibility with existing Innovair products, including remote accessories
Technical Specifications:
PHYSICAL SPECIFICATIONS | |
Size: (Rectangular Dimensions) (Square Dimensions) | 14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth |
Weight | 2.5 lbs (1.14 kg) |
Operating Temperature Range | D4120 & D4S: –4° to 158°F (–20° to 70°C); D4P120: –40° to 158°F (–40° to 70°C) |
Storage Temperature Range | D4120 & D4S: –22° to 158°F (–30° to 70°C); D4P120: –40° to 158°F (–40° to 70°C) |
Operating Humidity Range | 0% to 95% relative humidity non-condensing |
Air Duct Velocity | 100 to 4000 ft/min (0.5 to 20.32 m/sec) |
ELECTRICAL RATINGS | |
Power supply voltage | 20–29 VDC 24 VAC 50–60 Hz 120 VAC 50–60 Hz |
Input capacitance | 270 μF max. 270 μF max. N/A |
Reset voltage | 3.0 VDC min. 2.0 VAC min. 10 VAC min. |
Reset time: (with RTS151) | .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. |
Reset time: (by power down) | 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. |
Power up time | 35 sec. max. 35 sec. max. 35 sec. max. |
Alarm response time | 15 sec. 15 sec. 15 sec. |
Sensitivity Test | See detector label |
Max. standby current | 21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS @ 120VAC 60Hz |
Max. alarm current | 65 mA @ 24VDC 135 mA RMS @ 24VAC 60Hz 35 mA RMS @ 120VAC 60Hz |
CONTACT RATINGS | |
Alarm initiation contacts:(SPST) | 2.0A @ 30 VDC (resistive) |
Alarm auxiliary contacts:(DPDT) | 10A @ 30 VDC (resistive); 10A @ 250 VAC (resistive); 1⁄2 HP @ 240 VAC ; 1⁄4 HP @ 120 VAC |
Supervisory contacts: (SPDT) | 2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive) |