System Sensor Fire Alarm Control Panel

Provides enhanced feature set and advanced programming for all kinds of fire detection.

Description:

Honeywell System Sensor panels offer an out of the box and on the wall solution. A combination of quick installation, an enhanced feature set and advanced programming allows installers to quickly and simply meet the demands of the user. Equipped with configurable inputs, programmable relays, delay setting for alarm verification, software isolation of zone and NAC outputs, mapping of NAC to specific zones, password protections etc provide a wide variety of choice for system installers to customize the needs of an end user.

Product Features:

  • 16*2 Char LCD Display, Aesthetically designed Front Facia/LED’s
  • Individual Zone Isolation
  • Customizable text inserts
  • Input for remote reset/evacuate/alert/fire
  • Event Logging
  • Lamp Test Facility
  • Detectors/MCPs in same zone
  • Fire, Fault, Configurable Relay
  • Certified for Safety standard IEC 62368-1:2018
  • NAC Enable/Disable facility
  • Monitored NAC and Zone Circuit for Open/Short/Faults
  • Data/Time/Password configuration
  • One Man walk test facility
  • Up to 600 cable connectivity per zone, Typically 20 Detectors per zone+ 5 MCP’s
  • CE certificate
  • Earth Fault Monitoring
  • Battery Charging/Battery Internal Resistance Monitoring
  • Aux output facility
  • On board memory lock switch to prevent unauthorized panel configuration changes.
  • Configurable delays to output, with timer to fire indication
  • Mechanical Keylock

Technical Specifications:

MECHANICAL SPECIFICATIONS
Dimensions (H XW X D)360 X 422 X 122.8 mm (Front Facia),360 X 380 X 92.3 mm (Back Box)
Weight5.8 Kg Approx. (No Battery Fitted)
ConstructionPowder coated Cold Rolled STEEL1.2mm thick
Cable Entry15 X 20mm Knockout
Operating Temperature0 to 49°C
Relative Humidity5% to 95% Non-Condensing
ELECTRICAL SPECIFICATIONS
Operating Voltage230V-AC +/- 20% Output current 2A maximum, Alarm Load 1A Maximum
Standby BatteriesMinimum capacity 2 x 12 V 2.8Ah,Maximum capacity 2 x 12 V 7 Ah
Detection Circuit2, 4, 6, 8 zone, Max 2mA per Detector Circuit
Input TriggerExtended closing contact
Trigger External OutputsSounder Outputs:• 2 monitored outputs• 0.5 Amps per circuit

Auxiliary Output:• 18.5 to +28.5 Vdc, 0.5 Amp. (max)
HONEYWELLFire Alarm
Share: