BEAM 1224 Smoke Detector

A smoke detector designed for protecting open areas with high ceilings. 

Description:

System Sensor Model BEAM1224 is a four-wire conventional reflected beam smoke detector, which is uniquely suited for protecting open areas with high ceilings, where other methods of smoke detection are difficult to install and maintain. It is to be used with UL Listed compatible control panels only. An advantage of this single-ended reflective design is that it is much easier to install than the dual-ended projected beam detectors. Alignment is quickly accomplished via an optical sight and a two-digit signal strength meter incorporated into the product. Another advantage of the BEAM1224 is that it is listed for operation in temperatures ranging from –22°F to 131°F. This means it can be used in open areas to provide early warning in environments where temperature extremes may exceed the capability of other types of smoke detectors.

Product Features:

  • 16- to 328-foot protection range
  • Single-ended, reflective design
  • User-friendly alignment procedure
  • Six user selectable sensitivity levels
  • Optional integral NFPA 72 sensitivity test feature
  • Removable plug-in terminal blocks
  • Digital display for easy alignment
  • Built-in automatic gain control compensates for signal deterioration from dust build-up
  • Remote test station option
  • Paintable cover
  • Easiest alignment in the industry
  • Heater kits for transmitter/receiver and reflector option

Technical Specifications:

OPERATIONAL SPECIFICATIONS
Protection Range16 ft. to 328 ft. (5m to 100m)
Adjustment Angle+/– 10 Degrees horizontal & vertical(The optics move independent of the unit)
Sensitivity LevelsLevel 1 – 25%Level 2 – 30%Level 3 – 40%Level 4 – 50%Acclimate Level 1 – 30–50%Acclimate Level 2 – 40–50%
Fault Condition (Trouble)96% or more obscuration blockageIn alignment modeImproper initial alignmentSelf-compensation limit reached
Alignment AidOptical gunsightIntegral signal strength indication2-digit display
Alarm IndicatorLocal red LED and remote alarm
Trouble IndicatorLocal yellow LED and remote trouble
Normal indicatorLocal flashing green LED
Test/Reset FeaturesIntegral Sensitivity Test Filter (BEAM1224S only)Sensitivity filter (Incremental scale on reflector)Local alarm test switchLocal alarm reset switchRemote test and reset switch (Compatible with RTS451/RTS151 and RTS451KEY /RTS151KEY test station)
Smoke Detector SpacingOn smooth ceilings, 30–60 feet betweenprojected beams and not more than one-halfthat spacing between a projected beam and asidewall. Other spacing may be used dependingon ceiling height, airflow characteristics, andresponse requirements. See NFPA 72.
ENVIRONMENTAL SPECIFICATIONS
Temperature –22°F to 131°F (–30°C to 55°C)
Humidity10–93% RH Non Condensing
ELECTRICAL SPECIFICATIONS
Voltage10.2 to 32 VDC (BEAM1224)15 to 32 VDC (BEAM1224S)BEAM1224S should not be usedwith 12V power sources
Avg. Standby Current (24VDC)17mA Max
Avg. Current During Testing500mA Max
Avg. Alarm Current (24VDC)38.5mA Max
Avg. Fault Current (24VDC)8.5mA Max
Avg. Alignment Mode Current (24VDC)28mA Max
MECHANICAL SPECIFICATIONS
Detector Dimensions10 ̋ H × 7.5 ̋ W × 3.3 ̋ D(254mm H × 191mm W × 84mm D)
Reflector Dimensions (16′ to 230′)7.9 ̋ × 9.1 ̋ (200 × 230mm)
Reflector Dimensions(beyond 230′)15.7 ̋ × 18.1 ̋ (400 × 460mm)
ELECTRICAL SPECIFICATIONS (BEAMHK)
Voltage15 to 32V
Current92mA at 32V
Power consumption1.6W @ 24V; 3W @ 32V
HONEYWELLFire Alarm