MAD-401 and MAD-402 Series Addressable Modules 1 & 2 Technical Inputs

A device ideal for the supervision of any signal for fire control panels. 

Description:

The MAD-401 and MAD-402 modules are ideal for the supervising of any signal which may require supervision through a NC or NO contact (for example, the state of a door or a watertight door, or the monitoring of any type of sensors which provide free contact relay). The MAD-401 and MAD-402 modules take the power supply directly from the loop and assign a number of loop addresses according to the number of inputs available in the module.

Product Features:

  • Simple installation on the wall or fitted into a DIN rail
  • Non-polarity supported (only MAD-401 and MAD-402)
  • Addressing through a programmer
  • Loop-powered device
  • Connections through removable terminal blocks and simple fitting of the cable
  • EN 54-18 and EN 54-17 approved

Technical Specifications:

MODULE
Loop Features
Operating VoltageFrom 22 to 38VDC
Quiescent current consumption< 300 μA
Alarm current consumption3 mA
Technical input through a NC or NO contact (configurable)
CONNECTION
2 x 1,5 mm2twisted and shielded cable to a Z-200 base
ENVIRONMENT
Operating temperatureFrom -10°C to +70°C
Relative humidity95% without condensation
IP IndexIP40
TECHNICAL  FEATURES
Size 100 mm x 100 mm x 23 mm
MaterialABS
APPROVALS
EN 54-18 and EN 54-17 (only MAD-401-I and MAD-402-I)
MAD-401, MAD-402 Certificate number: 0370-CPR-1181
MAD-401-I, MAD-402-I Certificate number : 0370-CPR-1863
DETNOVFire Alarm
Share: