Designed to warm people in a building to start the evacuation procedure if necessary.
Description:
The range of addressable sounders MAD-46X-I has been designed to be used with Detnov’s addressable fire control panels and they conform to a basic device for warning signals in case of fire. The MAD-464-I addressable sounder is directly connected to the loop. It takes up to 1 address in the loop and needs to be directed by the PGD-200 programmer or by auto addressing.
Product Features:
- Compatible with Detnov’s addressable control panels
- Addressable sounder
- Low consumption
- Loop-powered device
- Connections through removable terminal blocks and simple fitting of the cable
- With isolator
- EN 54-3 and EN 54-17 approved
Technical Specifications:
MODULE | |
Loop Features | |
Operating Voltage | From 22 to 38VDC |
Quiescent current consumption | < 300 μA |
Alarm current consumption | <20 mA |
Volume | From 78,3 dB(A) to 104,6 dB(A) depends on the tone |
32 selectable tones3 configurable volumes: low, medium, high | |
CONNECTIONs | |
2 x 1,5 mm2 twisted and shielded cable | |
Maximum quantity of sounders in the loop:20 sounders in 1 km loop *10 sounders in 1 km loop | |
ENVIRONMENT | |
Operating temperature | From -10°C to 60°C |
Relative humidity | 95% without condensation |
IP Index | IP33C |
PHYSICAL FEATURES | |
Size | 100 mm x 75 mm |
Material | ABS |
APPROVALS | |
EN 54-3 y EN 54-17 | |
Certificate number: 0370-CPR-2664 |